Digitus Smart PDU, input monitored, input 1x16 A, outputs 20 x C13, 4 x C19

Digitus

DN-95640

New

Inlet monitored PDU,vertical,16A,20xC13,4xC19 3m cable, IEC60309 16A plug

Current distribution with remote monitoring options, in compact design for IT network and server racks.

Monitors various parameters with defined thresholds and alarm tools
Various measurements enable early detection of potential outages.
Up to five PDUs can be accessed with one IP connection; this makes simple and economical installation in your network possible.
Precise voltage and current measurement, with tolerances of +/-1%, guarantee reliable measurement results.
Monitoring of ambient conditions (e.g. temperature and humidity) with advance warning and alarm function.
Simple and quick installation in the rack with tool-free installation
Open data interface (e.g. SNMP, Modbus) for simple integration in the management system
Graphic display of measurement data with historical values supports faster troubleshooting
Clear local LCD shows measured values and the PDU status, for fast analysis on location.

The DIGITUS® Smart PDU measures the electronic parameters on the input. Definable thresholds with alarms increase the availability of connected users. The integrated communication card enables interconnection of up to 5 PDUs via one IP address as well as the remote monitoring and maintenance of all connected units. An integrated display shows all measured values and the PDU status. Additional external sensors (temperature, humidity, door contacts, smoke or water) can be connected to the communication card. The PDU can be installed without tools or permanently in DIGITUS® racks or other housing systems with appropriate mountings.

Current: 16 A
Input Plug: IEC 60309 16A 1ph/N/PE 6h
Installation: Rack 0U
Metering: PDU Metering
Outlets: IEC 60320 C13, IEC 60320 C19
Phase: 1ph
Power: 3,6 kVA
Volts: 230 V
Input monitoring: Current (A), voltage (V), energy (kWh), power (kW), power factor
User-defined thresholds for voltage and current
Comprehensive user-defined alarm management (remote and local)
2 sensor ports for the connection of external sensors (temperature, humidity, door contacts, smoke or water); expandable with an external sensor box
Daisy-chaining of up to five PDUs (including master device)
Internal storage of alarms and measured values (graphic display)
Firmware update of the PDU possible remotely or via USB
User management for up to 10 users
Remote connections: 10/100 Mbits Ethernet, serial RS485, USB
Protocols: HTTP(s), SSL, Telnet, TCP/IP, SNMP v1/v2/v3, DHCP, UDP, SSH, DNS, SMTP(s), NTP, Radius, Syslog, Modbus RTU
Encryption: TLS1.3
Input: Plug IEC60309 1ph/N/PE 6h, 230 V / 16 A
Output: Device sockets IEC60320 20 x C13 (max. 10 A per output), 4 x C19 (max. 16 A per output)
Cable: Cable cross section 2.5 mm², length: 3 m
Dimensions (mm, LxWxH): 1850 x 56 x 52
Temperature range (operation / storage): 0 °C to +45 °C/ -20 °C to +70 °C
Humidity range (operation / storage): 5% - 95% RH / 5 - 95% RH (non-condensing)
Maximum height above sea level (operation / storage): 0 - 3,000 m / 0 - 15,000 m
Approvals: CE conformity

Package content:
1 x Smart PDU, input monitored, 1-phase IEC60309 plug, 20 x C13, 4 x C19
1 x standard mounting bracket
1 x fastening tool for tool-free mounting
1 x Quickstart Guide

Platums(cm)214
Grums(cm)19.5
Augstums(cm)14.5
Svars(kg)10
Tilpums(cm3)60508.5
Izcelsmes valstsCN

19" accessories